| Sign In | Join Free | My carsrow.com | 
              
  | 
      
| Categories | PVC Insulated Cable | 
|---|---|
| Brand Name: | QINGDAO YICABLE CABLE | 
| Certification: | ISO,CE,KEMA GOST | 
| Place of Origin: | China | 
| MOQ: | 500m | 
| Price: | 0.3-99 USD/Meter | 
| Payment Terms: | L/C, D/A, D/P, T/T | 
| Supply Ability: | 5000KM per month | 
| Delivery Time: | 15 working days | 
| Packaging Details: | Wooden iron drum | 
| Application: | Industrial | 
| Type: | Low Voltage | 
| Insulation: | XLPE | 
| Rated voltage: | 0.6/1 kV | 
| Test Voltage: | 3.5 kV for 5 minutes | 
| Reference Standard: | IEC60502-1 | 
| Company Info. | 
| Qingdao Yilan Cable Co., Ltd. | 
| Verified Supplier | 
| View Contact Details | 
| Product List | 
Single Core 0.6/1kV PVC Insulated Power Cable for Power Transmission KEMA
Application
These power cable for fixed installations such as distribution
networks or industrial installations.
Such as Plant engineering; Industrial machinery; Heating and
air-conditioning systems; Power stations; Stage applications etc.
Construction
Conductor: Plain annealed copper, class 1 solid or class 2 stranded
acc. to IEC 60228.
Flexible class 5 or tinned conductor could be offer upon request.
Insulation: Cross-linked polyethlene (XLPE) compound as per IEC
60502-1.
Outer Sheath: PVC ST8 (90°C) of IEC 60502-1.
Outer Sheath Colour: Black or other color as per customer request.
Electrical Characteristics
Recommended rated voltages U0
| Highest system voltage(Um) (kV) | Rated voltage (U0) (kV) | |
| Categories A and B | Category C | |
| 1,2 | 0,6 | 0,6 | 
Routine test voltages
| Rated voltage U0 (kV) | 0,6 | 
| Test voltage (kV) | 3,5 | 
Maximum conductor temperatures for different types of insulating compound
| Maximum conductor temperature (°C) | |
| Normal operation | Short-circuit (5 s maximum duration)  | 
| 90 | 250 | 
Operating Temperature: -15°C to 90°C
Test Voltage: 3.5 kV for 5 minutes
Installation Refference
Min.Bending Radius (mm): 8 x cable overall diameter
Max.Pulling Tension (N/mm2): 70
Reference Standards
Design: IEC60502-1
Conductor: IEC60228, BS EN60228
Flame Retardancy: IEC 60332-1, BS EN60332-1

                                 
                             |