| Type | CP1H-XA CPU Units
 | CP1H-X CPU Units
 | CP1H-Y CPU Units | 
|---|
| Models | CP1H-XA[][][]-[] | CP1H-X[][][]-[] | CP1H-Y[][][]-[] | 
|---|
| Control method | Stored program method | 
|---|
| I/O control method | Cyclic scan with immediate refreshing | 
|---|
| Program language | Ladder diagram | 
|---|
| Function blocks | Maximum number of function block definitions: 128 Maximum number of
instances: 256 Languages usable in function block definitions: Ladder diagrams,
structured text (ST)
 | 
|---|
| Instruction length | 1 to 7 steps per instruction | 
|---|
| Instructions | Approx. 500 (function codes: 3 digits) | 
|---|
| Instruction execution time | Basic instructions: 0.10 μs min. Special instructions: 0.15 μs min. | 
|---|
| Common processing time | 0.7 ms | 
|---|
| Program capacity | 20K steps | 
|---|
| Number of tasks | 288 (32 cyclic tasks and 256 interrupt tasks) | 
|---|
|  | Scheduled interrupt tasks
 | 1 (interrupt task No. 2, fixed) | 
|---|
| Input interrupt tasks
 | 8 (interrupt task No. 140 to 147, fixed) | 6 (interrupt task No. 140 to 145, fixed) | 
|---|
| (Interrupt tasks can also be specified and executed for high-speed
counter interrupts.) | 
| Maximum subroutine number
 | 256 | 
|---|
| Maximum jump number | 256 | 
|---|
| I/O areas *
 | Input bits | 272bits (17 words): CIO 0.00 to 16.15 | 
|---|
| Output bits | 272bits (17 words): CIO 100.00 to 116.16 | 
|---|
| Built-in Analog Inputs
 | CIO 200 to CIO 203 | --- | 
|---|
| Built-in Analog Outputs
 | CIO 210 to CIO 211 | --- | 
|---|
| Serial PLC Link Area
 | 1,440 bits (90 words): CIO 3100.00 to CIO 3189.15 (CIO 3100 to CIO
3189) | 
|---|
| Work bits | 8,192 bits (512 words): W0.00 to W511.15 (W0 to W511) CIO Area: 37,504 bits (2,344 words): CIO 3800.00 to CIO 6143.15
(CIO 3800 to CIO 6143)
 | 
|---|
| TR Area | 16 bits: TR0 to TR15 | 
|---|
| Holding Area | 8,192 bits (512 words): H0.00 to H511.15 (H0 to H511) | 
|---|
| AR Area | Read-only (Write-prohibited): 7168 bits (448 words): A0.00 to
A447.15 (A0 to A447) Read/Write: 8192 bits (512 words): A448.00 to A959.15 (A448 to
A959)
 | 
|---|
| Timers | 4,096 bits: T0 to T4095 | 
|---|
| Counters | 4,096 bits: C0 to C4095 | 
|---|
| DM Area | 32 Kwords: D0 to D32767 | 
|---|
| Data Register Area | 16 registers (16 bits): DR0 to DR15 | 
|---|
| Index Register Area | 16 registers (32 bits): IR0 to IR15 | 
|---|
| Task Flag Area | 32 flags (32 bits): TK0000 to TK0031 | 
|---|
| Trace Memory | 4,000 words (500 samples for the trace data maximum of 31 bits and
6 words.) | 
|---|
| Memory Cassette | A special Memory Cassette (CP1W-ME05M) can be mounted. Note: Can be used for program backups and auto-booting.
 | 
|---|
| Clock function | Supported. Accuracy (monthly deviation): -4.5 min to -0.5 min (ambient temperature: 55°C),
 -2.0 min to +2.0 min (ambient temperature: 25°C),
 -2.5 min to +1.5 min (ambient temperature: 0°C)
 | 
|---|
| Communications functions | One built-in peripheral port (USB 1.1): For connecting Support
Software only. | 
|---|
| A maximum of two Serial Communications Option Boards can be
mounted. | 
| A maximum of two Ethernet Option Boards can be mounted. When using
CP1W-CIF41 Ver.1.0, one Ethernet Option Board can be mounted.
 | 
| Memory backup | Flash memory: User programs, parameters (such as the PLC Setup),
comment data, and the entire DM Area can be saved to flash memory as initial
values.
 Battery backup: The Holding Area, DM Area, and counter values
(flags, PV) are backed up
 by a battery.
 | 
|---|
| Battery service life | 5 years at 25°C. (Use the replacement battery within two years of
manufacture.) | 
|---|
| Built-in input terminals | 40 (24 inputs, 16 outputs) | 20 (12 inputs, 8 outputs) Line-driver inputs: Two axes for phases A,
 B, and Z
 Line-driver outputs: Two axes for CW and
 CCW
 | 
|---|
| Number of connectable Expansion (I/O) Units
 | CP Expansion I/O Units: 7 max.; CJ-series Special I/O Units or CPU
Bus Units: 2 max. | 
|---|
| Max. number of I/O points | 320 (40 built in + 40 per Expansion (I/O) Unit × 7 Units)
 | 300 (20 built in + 40 per Expansion (I/O) Unit × 7 Units)
 | 
|---|
| Interrupt inputs | 8 inputs (Shared by the external interrupt inputs (counter mode) and the quick-
 response inputs.)
 | 6 inputs (Shared by the external interrupt inputs (counter mode) and the quick-
 response inputs.)
 | 
|---|
| Interrupt input counter mode
 | 8 inputs (Response frequency: 5 kHz max. for all interrupt inputs), 16 bits
 Up or down counters
 | 6 inputs (Response frequency: 5 kHz max. for all interrupt inputs), 16 bits
 Up or down counters
 | 
|---|
| Quick-response inputs | 8 points (Min. input pulse width: 50 μs max.) | 6 points (Min. input pulse width: 50 μs max.) | 
|---|
| Scheduled interrupts | 1 | 
|---|
| High-speed counters | 4 inputs: Differential phases (4x), 50 kHz or
 Single-phase (pulse plus direction, up/
 down, increment), 100 kHz
 Value range: 32 bits, Linear mode or ring
 mode
 Interrupts: Target value comparison or
 range comparison
 | 2 inputs: Differential phases (4x), 500 kHz or Single-
 phase, 1 MHz and
 2 inputs:
 Differential phases (4x), 50 kHz or Single-
 phase (pulse plus direction, up/down,
 increment), 100 kHz
 Value range: 32 bits, Linear mode or ring
 mode
 Interrupts: Target value comparison or
 range comparison
 | 
|---|
| Pulse outputs
 (models
 with
 transistor
 outputs
 only)
 | Pulse outputs | Trapezoidal or S-curve acceleration and deceleration (Duty ratio: 50% fixed)
 4 outputs, 1 Hz to 100 kHz (CCW/CW or
 pulse plus direction)
 | Trapezoidal or S-curve acceleration and deceleration (Duty ratio: 50% fixed)
 2 outputs, 1 Hz to 1 MHz (CCW/CW or pulse
 plus direction)
 2 outputs, 1 Hz to 100 kHz (CCW/CW or
 pulse plus direction)
 | 
|---|
| PWM outputs | Duty ratio: 0.0% to 100.0% (Unit: 0.1%) 2 outputs, 0.1 to 6553.5 Hz (Accuracy: ±5% at 1 kHz)
 | 
|---|
| Built-in analog I/O terminals | 4 analog inputs and 2 analog outputs
 | None | 
|---|
| Analog control | 1 (Setting range: 0 to 255) | 
|---|
| External analog input | 1 input (Resolution: 1/256, Input range: 0 to 10 V), not isolated | 
|---|