| Sign In | Join Free | My carsrow.com |
|
| Categories | Air Cooled Screw Chiller |
|---|---|
| Brand Name: | ANGES |
| Model Number: | 170HP |
| Place of Origin: | China |
| MOQ: | 1 |
| Payment Terms: | T/T, L/C |
| Delivery Time: | 30 days |
| Packaging Details: | Plywood case |
| Compressor: | Hanbell |
| Expansion Valve: | Emerson |
| Condenser: | ANGES |
| Evaporator: | ANGES |
| Solenoid Valve: | Emerson |
| Drying Filter: | Emerson |
| Oil Pressure Gauge: | REFCO |
| Touch Screen: | WEINTEK |
| PLC Controller: | Siemens |
| Electrical components: | Schneider |
| Fan: | Maer |
| Company Info. |
| Shenzhen Anges Machinery Co., Ltd |
| Verified Supplier |
| View Contact Details |
| Product List |
Air Cooled Chiller High Efficiency Central Chiller For Plastic Injection Chiller System Industrial Chiller Manufacturers
What's the Air-cooled water chiller?
In an air-cooled chiller, hot refrigerant entering the copper tube fin condenser and it is exposed to atmospheric air, there're fan on top of the condenser for heat dissipation.The Air-cooled water chiller doesn't need cooling tower for operation, easier for installation and lower maintenance cost, due to no need treatment requirements.They are often a preferred choice especially in locations that water is shortage or very expensive.
Air Cooled Central Chiller for Plastic Injection Process
This Air-cooled screw central chiller is perfect choice that use for plastic process,such as plastic injection ,plastic extruding , bottle blowing, film blowing and son on.The industrial chiller used to transfer heat away from the mold and maintain a stable cooling rate and ensure the highest quality final products.
A central chiller means any chiller used for multiple process throughout a plant at the same time.It provides a continuous cold water to the process at a setting temperature.The system requires a water storage tank, internal circulations pump, process pumps to distribute the water to each process.
Air Cooled Central Chiller Specification
Model Parameter | AGS-170ADH | |
| nominal cooling capacity | kcal/h | 477988 |
| kw | 555.8 | |
| input power | kw | 181 |
| Max. Running current | A | 411.6 |
| power supply | 3PH~380V/50HZ | |
| refrigerant | type | R22 |
| refrigerating circuit | 1 | |
| type of control | expansion valve | |
| compressor | type | semi-hermetic screw |
| quantity | 1 | |
| Power | 76.8×2 | |
| start-up mode | Y-△ | |
| capacity control | 0-25-50-75-100 | |
| condenser | type | air cooled type finned copper tube |
| cooling air flow (m3/h) | 175000 | |
| power(kw) | 27 | |
| evaporator | type | shell and tube |
| quantity | 1 | |
| chilled fluid flow (m3/h) | 95.6 | |
| inlet and outlet pipe diameter (inch) | 6 | |
| safety protection | compressor over temperature, unit overload, high and low pressure, flow switch, phase sequence, phase-missing, anti-freezing | |
| net weight | kg | 4450 |
| Dimension | mm | 3150*4200*2200 |
Note: 1. Nominal cooling capacity is according to:
Inlet chilled fluid temperature:17℃
Outlet chilled fluid temperature: 12℃
Inlet cooling air temperature: 30℃
Outlet cooling air temperature:35℃
2. Working Range:
The temperature range of chilled fluid is from 5℃ to 30℃;
Temperature difference between inlet and outlet chilled fluid is from 3℃ to 8℃.
The machine can be used while the ambient temperature is below 40℃.
Some distinctive features of Air-cooled central screw type chillers:
|