| Sign In | Join Free | My carsrow.com |
|
| Categories | Smart Temperature Transmitter |
|---|---|
| Brand Name: | WNK |
| Model Number: | WNK6T-1 |
| Certification: | ISO |
| Place of Origin: | Hefei, China |
| MOQ: | 1 Set |
| Price: | Negotiable |
| Payment Terms: | T/T, Western Union, MoneyGram |
| Supply Ability: | 5000 pcs per month |
| Delivery Time: | 5-7 working days |
| Packaging Details: | Standard export carton packing |
| Temperature range: | 0~1300ºC, (Thermocouple K) |
| Voltage Input: | 9~45V (9~24V, Ex) |
| Signal Output: | 4~20mA/Hart/Profibus PA |
| Wetted Parts: | Aluminium 304SS, other custom materials |
| Accuracy: | 0.2%FS |
| Ex-proof: | ExiaII CT4 |
| Medium: | Liquid, gas and steam |
| Company Info. |
| Hefei WNK Smart Technology Co.,Ltd |
| Verified Supplier |
| View Contact Details |
| Product List |
4 -20ma Smart Temperature Transmitter And Temperature Gauge With Thermocouple Type K
WNK6T Series Temperature Transmitter with thermal couple(resistance) is an on-site installation type temperature transmitter of temperature series instruments. It consists of thermocouple, thermal resistance and temperature transmitter module, adopting two-wire system, with nonlinear calibration circuit, and can be used to directly measurement the temperature of liquid, gas media and special matter within -200C~+1300C during industrial process, converting temperature signal into current output signal of 4-20mADC which is linear to temperature signal, and sending to displayer, adjusting recorder or computer for total distributed control.
Advantages
1. High precision, digital precision up to :±0.01ºC
2.To reduce the overall cost of installation,maintenance and running
3. Install easily, more flexiable
4. LCD display, Menu-guided operation.
5, Self-diagnostics function
| Measuring media | liquid, gas and steam | ||
| Measuring range | -270~800 ºC (PT100 thermal resistor) | ||
| 0~1300ºC, (Thermocouple K) | |||
| Input | Thermocouple, RTD, MV, Resistive sensor | ||
| Power supply range | 9~45V (9~24V, Ex) | ||
| Output signal | 4~20mA/Hart/Profibus PA | ||
| Digital Accuracy | ±0.01ºC, PT100 input | ||
| Internal cold end compensation error | <0.25ºC±0.1%/10ºC | ||
| Temperature drift | ±0.05%/10ºCfull scale range | ||
| 0.1% between-10°C to 60°C | |||
| Effect of power supply on range | <0.005%/V full-scale range | ||
| Long term drift | <0.1/year | ||
|