| Sign In | Join Free | My carsrow.com |
|
| Categories | Industrial Control Relay |
|---|---|
| Brand Name: | SCHNEIDER |
| Model Number: | CAD32 CAD50 |
| Certification: | UL CE |
| Place of Origin: | FRANCE |
| MOQ: | 1 PCS |
| Price: | consult for best discount |
| Payment Terms: | T/T, , Western Union,Paypal,, MoneyGram,, L/C |
| Supply Ability: | 1000 |
| Delivery Time: | 2-7 days |
| Packaging Details: | schneider original package |
| product name: | TeSys CAD |
| Application: | Industrial Control |
| control circuit type: | AC 50/60 Hz |
| mounting support: | Rail Plate |
| mechanical durability: | 30 Mcycles |
| Condition: | New and Original |
| Company Info. |
| Yueqing Richuang Automation Equipment Co.,Ltd |
| Verified Supplier |
| View Contact Details |
| Product List |
Schneider TeSys CAD32 CAD50 Industrial Control Relay 220 VAC Contactor Relay
Applications
TeSys Control Relays are primarily used in industry, infrastructure and building applications for:
Easy to use interface for electronic devices (example: PLCs)
Benefits
TeSys Control Relays provide a cost-effective solution to a simple application.
Datasheet Of TeSys CAD Industrial Control Relay
| range | TeSys | |
|---|---|---|
| product name | TeSys CAD | |
| product or component type | Control relay | |
| device short name | CAD | |
| contactor application | Control circuit |
| utilisation category | AC-15 AC-14 DC-13 | |
|---|---|---|
| pole contact composition | 3 NO + 2 NC | |
| [Ue] rated operational voltage | <= 690 V AC 25...400 Hz | |
| control circuit type | AC 50/60 Hz | |
| [Uc] control circuit voltage | 220 V AC 50/60 Hz | |
| [Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947 | |
| [Ith] conventional free air thermal current | 10 A at <= 60 °C | |
| Irms rated making capacity | 140 A AC conforming to IEC 60947-5-1 250 A DC conforming to IEC 60947-5-1 | |
| [Icw] rated short-time withstand current | 100 A 1 s 120 A 500 ms 140 A 100 ms | |
| associated fuse rating | 10 A gG conforming to IEC 60947-5-1 | |
| [Ui] rated insulation voltage | 690 V conforming to IEC 60947-5-1 600 V certifications UL 600 V certifications CSA | |
| mounting support | Rail Plate |
| mechanical durability | 30 Mcycles | |
|---|---|---|
| operating rate | 180 cyc/mn | |
| inrush power in VA | 70 VA at 20 °C 50 Hz | |
| hold-in power consumption in VA | 8 VA at 20 °C 50 Hz | |
| minimum switching voltage | 17 V | |
| minimum switching current | 5 mA | |
| non-overlap time | 1.5 ms on de-energisation (between NC and NO contact) 1.5 ms on energisation (between NC and NO contact) | |
| insulation resistance | > 10 MOhm | |
| mechanical robustness | Shocks control relay open 10 Gn for 11 ms IEC 60068-2-27 Shocks control relay closed 15 Gn for 11 ms IEC 60068-2-27 Vibrations control relay open 2 Gn, 5...300 Hz IEC 60068-2-6 Vibrations control relay closed 4 Gn, 5...300 Hz IEC 60068-2-6 | |
| height | 77 mm | |
| width | 45 mm | |
| depth | 84 mm | |
| product weight | 0.58 kg |

|