Brand Name: Pearl Electric Co.,Ltd.
Model Number: PEC-S, SC(B) 9-15
Certification: KEMA, CE, CCC, ISO9001
Place of Origin: China
MOQ: 1 unit
Price: USD/RMB
Payment Terms: T/T, L/C
Supply Ability: 9000 units per year
Delivery Time: 30days-50days ex-work
Packaging Details: Seaworthy wooden packing
Core: Silicon steel sheet
Cooling: AN or customized
Capacity: 125KVA or Customized
Rated H. V.: 6.6Kv or Customized
Rated L. V.: 0.433kv or Customized
Impedance: 4% or Customized
  • Haven't found right suppliers
  • Our buyer assistants can help you find the most suitable, 100% reliable suppliers from China.
  • And this service is free of charge.
  • we have buyer assistants who speak English, French, Spanish......and we are ready to help you anytime!
  • Submit Buying Request
    • Product Details
    • Company Profile

    6.6 KV - 125 KVA Dry Type Transformer Low Noise Dry Type Cast Resin Transformer

    6.6kV - 125kVA Cast Resin Dry Type Transformer , Three Phases , Two Winding , Power Distribution​


    Product characteristic:
    1. It can be directly installed at the load center, which is free of maintenance and install conveniently, therefore it has low comprehensive running cost.
    2. With high moisture resistance, it runs normally at the moisture and can be put into operation without being dried after outage, with low loss and local discharge capacity.
    3. It has small noise, strong short circuit resistance and excellent environmental performance, and can run under severe environmental condition.
    4. It is safe, fire-retardant, fireproof and environment-friendly.

    Company situation

    The hoisting, tooling and testing equipment is complete. Pearl Electric has passed the ISO9001-2015 international standard quality management system certification. Adopting advanced technology and high quality raw material, with first class equipment and strict processing, SC-series resin casting dry type transformer. All performance indicators of the products have reached the relevant national standards and international standards.

    Pearl Electric's products are universally used in different industries, involving power plants, chemicals, construction, mining, metallurgy, rail transportation and so on. We do utmost to meet the needs of various users.


    Cast Resin Dry Type Transformer, Low Noise, Low Loss and Low Partial Discharge.

    No.ItemsUnit
    I Basic Information     
    1Rated Voltage ratiokV10kV / 0.433 kV
    1.01Rated CapacitykVA125
    1.02Applicable Standards IEC 60076
    1.03Manufacturer Pearl Electric
    1.04Country of Origin China
    II Electric Performance     
    2.06Insullation Class Class H
    2.07Temperature Rise (@40℃ ambient temperature)K125K
    2.08Cooling Method AN
    2.09Tapping Ranging ±2*2.5%
    2.1Vector Group Dyn11
    2.11Noise leveldB48
    2.12Impedance%4
    2.13No-load lossW530
    2.14Load Loss (@120℃)W1960
    2.15Local Partial dischargepC<10PC
    2.16Impulse Withstand Voltage (HV/LV)kV75/0
    2.17Power Frequency Withstand Voltage
    (HV/LV)
    kV28/3
    2.18Rated Duration of Short Circuits2
    III Materials & Accessories     
    3.01Core Materials Silicon Steel Sheet
    3.02Winding Materials Copper conductor/foil
    3.03Insulation methods HV vacuum cast / LV impregnant
    3.04Main Insulation Materials Epoxy Resin
    3.05Tap-changerpcsOff-load tap-changer
    3.06Sensor for Temperature Alarm and TrippcsYes, contact provided
    3.07Protective EnclosurepcsIP00


    Bushing

    • All bushings shall be in porcelain and will be fitted with firm fixing bracket.
    • The fuse carrying tube should be made of Non conductive and non breakable materials such as glass fiber and should be fitted with a provision for lowering and hoisting and fixing into the isolator base using a fuse carrier extraction rod/stick on a live circuit. The top of the fuse carrier should be provided with a screw cap to prevent rain water leakage.

    TECHNICAL DATA SHEET
    TECHNICAL GUARANTEE
    • The supplier shall join to his offer a data sheet including all characteristics of the proposed cut outs.
    • The supplier shall guarantee the equipment to be constructed in concordance with standard, all materials must be new and not already used , transformers shall be waterproof.
    TESTS:

    Tests shall be done in conformity referring to the manufacture standard as offered in his bid. All tests procedure shall be in accordance with referring standard.

    Design tests (type tests):

    A type test report in accordance to referring standard must be presented with offer. 5-2 Routine test:

    All routine tests must be performed by manufacture, results must be sent to the client before the date of acceptance test (in case of signature of contract).

    Acceptance tests:

    The acceptance tests will be held at the factory of the supplier. The client reserves the right to be represented at these tests.

    control on all line isolators.

    • Visual examination and verification on all isolators
    • Results of routine test examination.


    Applied Standard
    GB/T10228 , GB1094.11 , IEC60076-11 , DIN42523